Where flanges are used in data center cooling

A liquid-cooled data center moves heat from the chips to the atmosphere through a chain of water circuits. The flange specification changes along the way, from carbon steel waterworks flanges at the cooling towers to clean 316L at the rack manifolds.

Systems

What changes from loop to loop

Flange requirements by loop
FactorHeat rejection and chilled waterFacility water to CDUsTechnology cooling system
FluidTreated water, sometimes glycolTreated water or glycolInhibited water or PG25
Wetted metalCarbon steel commonCarbon or stainless steelStainless steel and copper alloys only
Usual standardB16.5 Cl 150, B16.47, AWWA C207B16.5 Cl 150, EN 1092-1 PN16B16.5 Cl 150, EN 1092-1 PN16
CleanlinessNormal construction practiceFlushed and treatedPickled, passivated, flushed to low conductivity

Read the guide to facility water and technology cooling loops for the definitions behind this table.