Every liquid-cooled data center has at least two water loops: the facility water system and the technology cooling system, joined at the coolant distribution unit. They look alike on a drawing but have very different rules for materials and cleanliness.

Updated 18 October 2026 · Rajendra Industrial Corporation

The facility water system (FWS) carries heat from the coolant distribution units to the building's heat rejection plant. The technology cooling system (TCS) is the closed, clean loop between the CDU and the IT equipment. The FWS may be carbon steel; the TCS must be stainless steel or other approved wetted materials.

The loops in order

Water loops in a liquid-cooled data center, from the chip outward
LoopRuns betweenTypical fluid
Technology cooling system (TCS)Cold plates and rack manifolds to the CDUInhibited water or propylene glycol, for example PG25
Facility water system (FWS)CDU heat exchanger to chillers, dry coolers or heat exchangersTreated water, sometimes glycol
Condenser water systemChiller condensers to cooling towersTreated, open-loop water

In some designs the FWS is the chilled water loop itself. In others, the FWS is a separate warm water loop fed by dry coolers with chillers only for trim. The principle is the same: the CDU's heat exchanger is the boundary.

Temperatures: ASHRAE W classes

ASHRAE TC 9.9 classifies facility water supplied to liquid-cooled IT equipment by its maximum supply temperature. In the fifth edition of its thermal guidelines the classes were renamed after their upper limits:

ASHRAE liquid cooling classes for facility water
ClassMaximum facility water supplyEarlier name
W1717 °CW1
W2727 °CW2
W3232 °CW3
W4040 °CNew in the fifth edition
W4545 °CW4
W+Above 45 °CW5

Warmer classes allow more free cooling and heat reuse. For flanges, these temperatures are mild: all the usual grades keep most of their ambient pressure rating. Gaskets are more sensitive to temperature, so check them at the design temperature.

Side by side

FWS and TCS compared
FactorFacility water systemTechnology cooling system
PurposeMoves heat from CDUs to the plantMoves heat from chips to the CDU
Wetted metalsCarbon steel, stainless steel, copperStainless steel and copper alloys only
CleanlinessBuilding water treatmentFiltered to as fine as 5 µm; low conductivity
Size rangeLarge mainsSmaller headers and manifolds
Usual flangeA105 or stainless, B16.5 Cl 150 or PN16316L, B16.5 Cl 150 or PN16, pickled and passivated
Joint typesWeld neck, slip-on, flat face at cast ironWeld neck, stub end with lap joint
Why the TCS is strict

Cold plate microchannels are about 100 microns wide. IBM's water-cooling specification rules out plain carbon steel on the loop because it rusts and fouls, and the Open Compute Project sets stainless steel of at least grade 304 for TCS piping, delivered with surfaces treated to ASTM A380.

What it means for the flange schedule

  • Split the flange schedule by loop. Material, finish and inspection rules differ.
  • On the TCS, order 316L or 304L flanges, pickled and passivated, with 100% PMI.
  • On the FWS, follow the operator's specification: carbon steel A105 is common, stainless is increasingly used near the white space.
  • Where carbon steel FWS meets a stainless CDU, decide whether to isolate the joint.

Frequently asked questions

Is the TCS the same as the secondary fluid network?

Yes. Technology cooling system (TCS) is the ASHRAE term. Some suppliers call the same loop the secondary fluid network (SFN) or simply the secondary loop.

Can the facility water flow straight through the cold plates?

Some systems do this, but most liquid-cooled data centers separate the loops with a CDU so that the IT equipment sees only clean, controlled coolant, and a leak or contamination on one side does not reach the other.

Which loop needs stainless steel flanges?

The TCS, always. The facility water system can be carbon steel, stainless steel or a mix, depending on the operator's specification.

Sources

  • ASHRAE TC 9.9, Thermal Guidelines for Data Processing Environments, fifth edition (liquid cooling classes)
  • Open Compute Project, guidelines for pre-commissioning preparation of TCS row manifolds
  • IBM, water cooling system specification and requirements

Request for quotation

Send us your flange schedule

A line list, a BOM or a marked-up drawing all work. For each line item, tell us:

  • Flange type, face and size (NPS or DN)
  • Standard and pressure class, for example ASME B16.5 Class 150 or EN 1092-1 PN16
  • Material grade and the loop it goes on, for example 316L on the TCS loop
  • Quantity, inspection requirements and destination