Guide

Stainless vs carbon steel flanges for data center cooling

The choice between stainless and carbon steel flanges in a data center is not a question of quality. It depends on which loop the flange is on, what touches the water, and how clean the loop has to stay.

Updated 18 October 2026 · Rajendra Industrial Corporation

Use stainless steel (316L or 304L) for every flange that touches the technology cooling system coolant, and at the CDU secondary side. Use carbon steel (A105, or A350 LF2 where it gets cold) for condenser water and most chilled water and facility water, unless the operator's specification calls for stainless.

Decision by loop

Flange material by loop
LoopRecommendedAcceptableAvoid
Technology cooling system316L304LCarbon steel, galvanised steel
CDU secondary side316L304LCarbon steel
CDU primary sideMatch the facility water pipingStainless with isolation kit to carbon steel-
Facility water mainsA105 or per operator spec304L / 316L-
Chilled water plantA105Stainless where specified-
Condenser waterA105; AWWA C207 on large mainsA350 LF2 in cold climates-

Corrosion behaviour

Carbon steel relies on the water chemistry for protection. In a closed, inhibited chilled water loop with low oxygen, corrosion rates are low, which is why it is the long-standing standard for building hydronics. Stainless steel protects itself with a thin chromium oxide film. It does not need inhibitors to stay passive, and it does not shed iron oxide into the water, which is what makes it the material for loops feeding cold plates.

Stainless is not immune. Chlorides can cause pitting, and heat tint left after welding lowers corrosion resistance. 316L's molybdenum helps against chlorides, and pickling and passivation restores the surface after fabrication.

Ratings and dimensions

ASME B16.5 Class 150 rating at -29 to 38 °C
MaterialGroupClass 150 rating
A105, A350 LF21.119.6 bar (285 psi)
F304, F3162.1, 2.219.0 bar (275 psi)
F304L, F316L2.315.9 bar (230 psi)

Dimensions do not change with material: a Class 150 NPS 8 flange has the same bolt circle in A105 and 316L. Only the rating changes, and for data center water pressures, Class 150 has margin in every grade.

Transitions

The usual transition is at the CDU, where a carbon steel facility water main meets stainless equipment. Water conducts current between the metals, and the carbon steel near the joint corrodes faster. Many specifications put an insulating gasket kit at that flange. See how isolation kits work.

Cost

Stainless flanges cost more than carbon steel. On large stainless lines, a stub end with a lap joint flange keeps the wetted part in 316L while the loose flange can be a lower cost material.

Frequently asked questions

Is stainless steel always the safer choice?

For wetted parts on the TCS, yes. On the facility side, carbon steel with good water treatment has a long track record, and stainless adds cost without always adding benefit. Use the loop and the operator's specification to decide.

Does 316L have the same pressure rating as A105?

No. At ambient temperature a Class 150 flange is rated 15.9 bar in 316L (ASME B16.5 group 2.3) and 19.6 bar in A105 (group 1.1). Both are well above typical data center water pressures.

Can we mix stainless and carbon steel flanges in one system?

Yes, at defined transitions such as the CDU primary connection. Consider an insulating gasket kit at the joint, and never put carbon steel on the clean TCS side.

Request for quotation

Send us your flange schedule

A line list, a BOM or a marked-up drawing all work. For each line item, tell us:

  • Flange type, face and size (NPS or DN)
  • Standard and pressure class, for example ASME B16.5 Class 150 or EN 1092-1 PN16
  • Material grade and the loop it goes on, for example 316L on the TCS loop
  • Quantity, inspection requirements and destination